kVA vs kW

kW is the real power that does work; kVA is the total (apparent) power the supply must deliver. Power factor links them.

kW = kVA × power factor

kVA = kW ÷ power factor · kVAR = √(kVA² − kW²)

Sizing a generator or UPS

Generators are rated in kVA at a power factor of 0.8, so a 10 kVA DG set delivers about 8 kW. Add up your load in kW, divide by 0.8, and add 20–25% for motor starting currents and future needs.

Home inverters

Home inverters are rated in VA; their usable watts are usually 0.7–0.8 of the VA rating. A 1,000 VA inverter supports roughly 700–800 W of load.

Related calculators

Frequently asked questions

How many kW is 1 kVA?

At a power factor of 0.8, 1 kVA = 0.8 kW. At PF 1 (purely resistive loads), 1 kVA = 1 kW.

What size generator do I need for 8 kW?

8 ÷ 0.8 = 10 kVA, so a 12.5 kVA set gives a sensible margin, especially if you have motors or ACs.

Why is kVA higher than kW?

Motors and electronics draw some current that doesn't do useful work (reactive power). The supply must still provide it, so kVA ≥ kW.