Wire Size for House Wiring: Which sq mm for Which Load

A wire size and MCB chart for home circuits, how to find the current, and the voltage drop check for long runs.

By Team Vind · Updated · 5 min read

Undersized wiring is the commonest cause of electrical fires in Indian homes. A wire that's too thin for its load runs hot, its insulation breaks down, and one day it shorts. The fix is cheap if you get it right at the time of wiring: choose the size by the current it must carry and how far it runs.

Wire sizes used in homes

House wire is sold by the cross-section of its copper in square millimetres (sq mm). Each size goes with a usual MCB rating:

Copper wireUsual MCBLoad it can serve at 230 VTypical use
1 sq mm6 Aup to about 1,100 WLighting
1.5 sq mm10 Aup to about 1,800 WLights and fans
2.5 sq mm16 Aup to about 2,900 WPower sockets, 1–1.5 ton AC
4 sq mm20 Aup to about 3,700 WGeyser, 2 ton AC, kitchen
6 sq mm32 Aup to about 5,900 WHeavy loads, sub-mains
10 sq mm40 Aup to about 7,400 WSub-main to a floor
16 sq mm63 Aup to about 11,600 WMain supply
Common practice for copper PVC-insulated wire in conduit. Load shown is 80% of the MCB rating, the limit for continuous use.

Step 1: find the current

Current (A) = watts ÷ (230 × power factor)

AppliancePowerCurrentUsual circuit
LED lights and fans (one room)300 W1.4 A1.5 sq mm on a 10 A MCB
Refrigerator (6 A socket)200 W1 A1.5 sq mm on a 10 A MCB
Washing machine500 W2.6 A2.5 sq mm on a 16 A MCB
Microwave or induction cooktop2,000 W8.7 A2.5 sq mm on a 16 A MCB
1.5 ton air conditioner1,700 W8.2 A2.5 sq mm on a 16 A MCB
Geyser (15–25 litre)2,000 W8.7 A4 sq mm on a 20 A MCB
2 ton air conditioner2,300 W11.1 A4 sq mm on a 20 A MCB
Heaters have a power factor of 1; motors and compressors are lower, so they draw more current per watt.

Give every air conditioner, geyser and kitchen power point its own circuit and MCB. More on the sums in watts, volts and amps.

Try it: Wire Size Calculator

Load and Cable

W
m
%

A guide only. Have a licensed electrician confirm sizes and MCBs.

Suggested Wire Size

4 sq mmWire size
14.49 ALoad current
3.88 V (1.69%)Voltage drop
2.25 sq mm
Minimum for voltage drop
4 sq mm
Minimum for current

Commonly used copper wire sizes in homes

WireUsual MCBTypical use
1 sq mm6 ALighting
1.5 sq mm10 ALights and fans
2.5 sq mm16 APower sockets, 1–1.5 ton AC
4 sq mm20 AGeyser, 2 ton AC, kitchen
6 sq mm32 AHeavy loads, sub-mains
10 sq mm40 ASub-main to a floor
16 sq mm63 AMain supply

Step 2: check the voltage drop on long runs

Every metre of wire wastes a little voltage. Too much, and motors run hot, ACs trip and lights dim. Keep the drop within about 3% (roughly 7 V on 230 V).

Voltage drop = 2 × ρ × length × current ÷ area

Here ρ is the resistivity of warm copper, 0.0214 Ω·mm²/m, and the 2 covers the journey out and back. A 3,000 W load 40 m from the distribution board draws 14.5 A:

WireVoltage dropAs % of 230 VVerdict
2.5 sq mm9.92 V4.32%Too much: go one size up
4 sq mm6.2 V2.7%Fine
6 sq mm4.14 V1.8%Fine

So for a long run, the wire often has to be a size larger than the current alone suggests. Doubling the length doubles the drop.

The rule that prevents fires

Buying wire: what to look for

  • Copper, not aluminium, for wiring inside the house. Aluminium needs about 1.6 times the cross-section for the same current and loosens at joints over time.
  • ISI mark (IS 694) and a known brand. Underweight wire with less copper than marked is a common fraud: a 90 m coil should weigh what the maker's chart says.
  • FR or FRLS insulation. FR (flame retardant) is the minimum; FRLS (low smoke) is better for flats and closed spaces.
  • Colour code: red, yellow or blue for phase, black for neutral, green for earth.
  • Earth every circuit, and fit an RCCB (ELCB) of 30 mA at the distribution board to protect against shocks.

Planning backup power too? See inverter battery backup time and kVA vs kW.

Frequently asked questions

Which wire size is used for a 1.5 ton AC?

Usually 2.5 sq mm copper on its own 16 A MCB for a short run. A 1.5 ton AC of about 1,700 W draws around 8.2 A. Long runs or 2 ton units normally use 4 sq mm on a 20 A MCB.

Which wire is used for house wiring in India?

ISI-marked (IS 694) copper wire with FR or FRLS insulation: commonly 1 to 1.5 sq mm for lighting, 2.5 sq mm for power sockets, 4 sq mm for heavy appliances and 6 sq mm or more for sub-mains.

How do I calculate the wire size for a load?

Find the current (watts ÷ 230 ÷ power factor), choose a wire and MCB rated at least 1.25 times that, then check that the voltage drop over the cable length stays within about 3%.

Can I use 1.5 sq mm wire for a geyser?

No. A 2,000 W geyser draws about 8.7 A continuously and is normally wired in 2.5 or 4 sq mm copper on a 16 or 20 A circuit of its own.