Wire Size for House Wiring: Which sq mm for Which Load
A wire size and MCB chart for home circuits, how to find the current, and the voltage drop check for long runs.
By Team Vind · Updated · 5 min read
Undersized wiring is the commonest cause of electrical fires in Indian homes. A wire that's too thin for its load runs hot, its insulation breaks down, and one day it shorts. The fix is cheap if you get it right at the time of wiring: choose the size by the current it must carry and how far it runs.
Wire sizes used in homes
House wire is sold by the cross-section of its copper in square millimetres (sq mm). Each size goes with a usual MCB rating:
| Copper wire | Usual MCB | Load it can serve at 230 V | Typical use |
|---|---|---|---|
| 1 sq mm | 6 A | up to about 1,100 W | Lighting |
| 1.5 sq mm | 10 A | up to about 1,800 W | Lights and fans |
| 2.5 sq mm | 16 A | up to about 2,900 W | Power sockets, 1–1.5 ton AC |
| 4 sq mm | 20 A | up to about 3,700 W | Geyser, 2 ton AC, kitchen |
| 6 sq mm | 32 A | up to about 5,900 W | Heavy loads, sub-mains |
| 10 sq mm | 40 A | up to about 7,400 W | Sub-main to a floor |
| 16 sq mm | 63 A | up to about 11,600 W | Main supply |
Step 1: find the current
Current (A) = watts ÷ (230 × power factor)
| Appliance | Power | Current | Usual circuit |
|---|---|---|---|
| LED lights and fans (one room) | 300 W | 1.4 A | 1.5 sq mm on a 10 A MCB |
| Refrigerator (6 A socket) | 200 W | 1 A | 1.5 sq mm on a 10 A MCB |
| Washing machine | 500 W | 2.6 A | 2.5 sq mm on a 16 A MCB |
| Microwave or induction cooktop | 2,000 W | 8.7 A | 2.5 sq mm on a 16 A MCB |
| 1.5 ton air conditioner | 1,700 W | 8.2 A | 2.5 sq mm on a 16 A MCB |
| Geyser (15–25 litre) | 2,000 W | 8.7 A | 4 sq mm on a 20 A MCB |
| 2 ton air conditioner | 2,300 W | 11.1 A | 4 sq mm on a 20 A MCB |
Give every air conditioner, geyser and kitchen power point its own circuit and MCB. More on the sums in watts, volts and amps.
Try it: Wire Size Calculator
Step 2: check the voltage drop on long runs
Every metre of wire wastes a little voltage. Too much, and motors run hot, ACs trip and lights dim. Keep the drop within about 3% (roughly 7 V on 230 V).
Voltage drop = 2 × ρ × length × current ÷ area
Here ρ is the resistivity of warm copper, 0.0214 Ω·mm²/m, and the 2 covers the journey out and back. A 3,000 W load 40 m from the distribution board draws 14.5 A:
| Wire | Voltage drop | As % of 230 V | Verdict |
|---|---|---|---|
| 2.5 sq mm | 9.92 V | 4.32% | Too much: go one size up |
| 4 sq mm | 6.2 V | 2.7% | Fine |
| 6 sq mm | 4.14 V | 1.8% | Fine |
So for a long run, the wire often has to be a size larger than the current alone suggests. Doubling the length doubles the drop.
The rule that prevents fires
Buying wire: what to look for
- Copper, not aluminium, for wiring inside the house. Aluminium needs about 1.6 times the cross-section for the same current and loosens at joints over time.
- ISI mark (IS 694) and a known brand. Underweight wire with less copper than marked is a common fraud: a 90 m coil should weigh what the maker's chart says.
- FR or FRLS insulation. FR (flame retardant) is the minimum; FRLS (low smoke) is better for flats and closed spaces.
- Colour code: red, yellow or blue for phase, black for neutral, green for earth.
- Earth every circuit, and fit an RCCB (ELCB) of 30 mA at the distribution board to protect against shocks.
Planning backup power too? See inverter battery backup time and kVA vs kW.
Frequently asked questions
Which wire size is used for a 1.5 ton AC?
Usually 2.5 sq mm copper on its own 16 A MCB for a short run. A 1.5 ton AC of about 1,700 W draws around 8.2 A. Long runs or 2 ton units normally use 4 sq mm on a 20 A MCB.
Which wire is used for house wiring in India?
ISI-marked (IS 694) copper wire with FR or FRLS insulation: commonly 1 to 1.5 sq mm for lighting, 2.5 sq mm for power sockets, 4 sq mm for heavy appliances and 6 sq mm or more for sub-mains.
How do I calculate the wire size for a load?
Find the current (watts ÷ 230 ÷ power factor), choose a wire and MCB rated at least 1.25 times that, then check that the voltage drop over the cable length stays within about 3%.
Can I use 1.5 sq mm wire for a geyser?
No. A 2,000 W geyser draws about 8.7 A continuously and is normally wired in 2.5 or 4 sq mm copper on a 16 or 20 A circuit of its own.
Sources
- Bureau of Indian Standards: IS 732, code of practice for electrical wiring installations
- Bureau of Indian Standards: IS 694, PVC insulated cables for working voltages up to 1,100 V
Last reviewed: 12 October 2026